Copyright © 2025 KVMGalore® - All rights reserved.
Operations
• Measurement Range: Wet or Dry
• Sensor Type: Open/Closed contact input switch
• Measurement Rate: Multiple readings every second
• Capable of detecting the presence of fuel and oil at a specific location within 1 meter, or 1 foot along the length of the sensing rope
• Full autosense including disconnect alarm
• Sensor count: 1
• Nonresettable: Must be replaced after exposure to hydrocarbon liquids
• Indication: LED for Status
Typical response time at 20°C (68°F)
• Gasoline: 2-12 minutes (depending on the grade and type)
• Diesel #1: 60 minutes
• Jet AB58: 50 – 70 minutes
• JP-457: 15 – 70 minutes
• Kerosene: 47 minutes
Physical
• Pull Force Limit: Not to exceed 50 lb
• Bend Radius: 2 in. (50 mm) minimum
• Pressure Loads: Greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger an alarm
• 10 foot rope portion (the liquid sensing cable)
• 20 foot non-sensing leader cable (from the rope to the sensing module)
• 5 foot CAT-5 cable (from the sensing module to the monitoring appliance's intelligent sensor port)
• Main Sensing Module Dimensions: 2.2 x 2.16 x 1.31 in. (56 x 55 x 33.3 mm)
• Mounting: Screw mounting and DIN rail mounting
• Cable Diameter: 0.28 in. (7 mm) nominal
Interface
• Communications Interface Cable: RJ-45 jack on main sensing module to monitoring appliance's intelligent sensor port
• Communications Interface Cable: CAT-5 UTP
• Communications Interface Cable Max. Length: 100 feet
Environment / Power
• Powered by the controller unit - no additional power needed
• Power Consumption: Typical 125 mWatt, 25 mA
• Operating Temperature: 4°~140°F (-20°~60°C)